Parallel Network Interface (PNI)

 

Beginning with PSCAD v4.6, multiple case projects representing multiple parts of a complete electric network, can be run simultaneously as a single simulation. A single electric network may be split so that each electric subsystem is represented by a separate case project, and thereby run using a separate EMTDC process. Each EMTDC process is linked together via an Parallel Network Interface (PNI) to form a cohesive simulation that is run from within a single workspace.

 

 

Multi-Project Simulation Using the PNI in PSCAD

 

In terms of runtime information for plotting and online data signal control, PSCAD and EMTDC communicate normally as they would for a single process. There is additional communication between the multiple EMTDC processes in multi-project simulations however. Due to the fact that each EMTDC process is an executable file, each can be launched on its own processor core, enabling parallel simulation of the complete system.

 

For larger networks containing multiple subsystems, using the PNI can greatly enhance the total simulation speed, especially when the subsystems contain high speed switching devices (i.e. FACTs devices).

Setting Up the PNI

The boundaries of electric subsystems in EMTDC are defined via distributed-parameter transmission lines and cables, and so it makes sense that the transmission segments themselves be the linking points in a multi-project simulation. As a very simple example, let us take a slightly modified version of the familiar Cigre Benchmark Model example project. A transmission line has been added to represent the DC interconnection between the two converters (the original was simply an RLC passive network).

 

Cigre Benchmark Model Example Project with Transmission Line Interconnect

 

The addition of the transmission line to this system results in a division of the electric network into two, separate subsystems (approximately 25 nodes each). These two sub-networks can be compiled and launched as separate, but dependent processes, due to the natural propagation delay generated by the distributed transmission line. Before this can be accomplished however, the project must be manually split in to two separate project files.

 

Splitting the project up can be achieved in a number of ways, but the most efficient is to first make a duplicate of the original project and then manually modify each one. Doing this for this example results in the following two separate project circuits:

 

Rectifier Side Project

Inverter Side Project

 

In order to accommodate this new electric network interface between projects, some changes have been made to the transmission line components. These changes are explained in the following sections.

Transmission Line and Cable Parameters

A few parameters and functionalities exist in both the Overhead Line and Cable configuration, as well as the Overhead Line and Cable interface components in order to accommodate the PNI interface. In the configuration components, two new termination styles have are provided.

 

 

Of the four options provided, only Foreign and Alien ends are used when setting up the PNI interface:

The interface components contain a few parameters involving the ENI:

 

 

These parameters provide information for the Control Signal Carrier function (described below).

There is also a parameter provided for using the PNI between separate PSCAD applications:

 

Control Signal Carrier

Inevitably when a project is decomposed into separate electrical subsystems, there will be situations where control signals generated in one project are needed in another. The PNI utilizes a concept referred to Control Signal Carrier, which allows control signals to be piped through the transmission line interface, along with the electrical data. Of course, the control signal data arrives at the other end with no time delay.

 

In the example given above, the Current Order control signal is generated in the inverter case project, and then passed via control signal carrier to the rectifier project.

 

Project 1 Transmission Line End Exchanging Control Signal Data with Project 2

Project 2 Transmission Line End Exchanging Control Signal Data with Project 1

Transmission Line Interface Component Parameters